CIO modules for CAN bus are passive input/output modules based on PCA82C150 chip from Philips. They are used for increasing of NLC-3 input/output number or as inputs and outputs of VTT-2, VTT-3 terminals end NDS intelligent panel meter. They also can be used by controllers from other producers, which are able to communicate by Philips SLIO controllers. CIO modules are inbuilt in plastic housing for DIN rail from Weidmuller with metal top cover. Input circuits, logic circuits and communication circuits are galvanically decoupled. Binary inputs are hardware filtered - the minimum registered pulse length is 3 millseconds. Modules are powered by 24 V DC. Module address is selected by jumper under top cover. The maximum number of CIO modules at one CAN bus segment is 16. Maximum baud rate for CAN bus with implemented CIO modules is 125 kbit/sec. Produced types:
|
Power source | |
Power voltage Power current-by module type CIO 8 8R CIO 16I 0 CIO 0 16R Indicated by LED |
24V±10% DC max. 200 mA max. 70 mA max. 400 mA |
CAN interface | |
Physical interface Recessive state VCAN-H VCAN-L Dominant state VCAN-H VCAN-L |
by ISO 11898 2.5V 2.5V 3.5V 1.5V |
Binary Inputs | |
Number | max. 16, 24V DC |
Relay Outputs | |
Number | max. 16, 230V 8A |
Indication | |
IO state | by LEDs |
Mechanical Description | |
Mounting Dimmensions CIO88T,CIO16I Mass Dimmensions CIO88R,CIO16R Mass |
for DIN rail 35mm 160 x 105 x 60 mm 400 g 210 x 105 x 60 mm 800 g |
Working conditions | |
Temperature range Protection |
0 ~ 50°C IP20 |
Connection | |
Connection |
screw terminals wire cross-section max. 2,5mm2 |